My Switch Supervisor Analog

The most essential device in the electrical panel, after the residual current device (RCD).

This manual is intended exclusively for professional electrical installers.
All the tasks described here must be performed exclusively and only by specialized personnel.

In your hands, you have a new innovative device – a supervisor – which controls the full operation of the electric water heater, offering the user the ability to save money, safety, and health.

The device My Switch MSS-21 It is DIN rail mounted and has all certifications according to the EU directive. EN-60730-1 and EN-60730-2-7 and is certified for an operating voltage from 90V up to 240V AC and current intensity 25A.

It is activated by pressing the button START and, without any other adjustment, supplies power to the water heater for the required time until the water is heated.
The supervisor My Switch MSS-21 It controls the electric current flow to the water heater’s heating element and automatically turns off when the water is heated and the thermostat cuts off the current flow.

The device also features a timer that acts as a safety time step, which intervenes and shuts off the water heater in case of thermostat failure.

The safety time is selectable between 30, 60 and 90 minutes..
The default time has been set to 60 λεπτά. ( In areas with low temperatures and large water heater capacity, the 90-minute time is recommended ) .

The controller is equipped with a command gateway.The gateway can receive activation commands from a wired or wireless button, as well as through various applications. (app),  Smart Home and Wi-FI with the connection WiFi Module.

The output gateway provides the ability to report the activation and deactivation of the device.

Installation and wiring instructions

Before performing any action, please carefully read the instructions by following the steps below and correctly using the wiring diagram.

Η λειτουργία του θερμοσίφωνα μπορεί να ελέγχεται και από μακριά μέσω εξωτερικού διακόπτη επαναφοράς (ενός ή περισσοτέρων), στις επαφές 3 & 4.

At terminal 3, you have a positive output for connecting an indicator LED.

If you wish to have remote control via phone, choose the MSS-24 Wi-Fi device.

More information about features and wiring can be found in the attached PDF.
Before handing over the project, testing is required to confirm that the device is functioning correctly. 
 

Verification of wiring and proper operation

The following steps are provided for checking the proper operation of the device.

• If the green LED If the green LED turns on and off, check if the water is already warm.
If it is not, and no wiring issues are detected, there may be a fault in the water heater.

Technical specifications:

Operating voltage from 90V AC to 240V AC

Current rating 25A max (caution: Do not connect devices with higher current, risk of device overheating)

Frequency 50/60 Hz

Powered by: